Manual for InduXEL222

Manual for InduXEL222

Brand: ABB

Category: Lighting

Document Type: Manual

Language: EN

Uploaded: April 20, 2026, 7:52 p.m.

Warranty Information

Self-contained InduXEL222 range guaranteed for 3 years; batteries for 2 years.

These emergency lighting units are designed for potentially explosive atmospheres (ATEX) Zone 2, 22. They are NF AEAS approved and comply with various EN and NF standards. The luminaires are Class II with limited surface temperature, suitable for environments with conductive dust accumulation.

Key features include autotest functions (SATI), compatibility with the Naveo®Pro supervision application, and specific installation and maintenance requirements for hazardous areas.

Batteries must be replaced when operating time is insufficient, using Hazlux® parts by qualified personnel. The light source is not replaceable; the entire luminaire must be replaced at end of life.

Troubleshooting and error codes

Status Explanation Cause Action
Green LED fixed + yellow LED off No problem
Yellow LED fixed + sidelight LEDs off Luminaire OK
Yellow LED fixed + sidelight LEDs on Charging failure Battery disconnected Reconnect the battery (If the failure persists = factory return)
Yellow LED blinking Autonomy failure Battery failed the duration test Replace the battery
Green LED blinking Test in progress Weekly and trimestriel tests
Double pulsing green LED Delayed test Autonomy test launched while the luminaire is insufficient charge Return to factory
Privacy Policy