Normal Operation: The green indicator light on the face plate stays on. The LED will go out if the mains supply fails, the internal charger malfunctions, or the unit is in test mode.

Test Switch: Pressing the test switch button will cause the LED indicator to go out and the sign to illuminate using the battery pack.

Commissioning Test Behaviour: Upon initial mains supply connection, a commissioning sequence starts, charging the battery for an uninterrupted 60 hours. Interruptions reset this timer. This is followed by a 24-hour charge, a duration test, another 24-hour charge, and a function test. The gear then proceeds to automated tests or DALI-controlled tests.

Gear Behaviour After Battery Change: After a battery change, the gear will perform a complete commissioning sequence regardless of the battery's condition.

Function Test: A 5-second functional test is conducted approximately weekly.

Duration Test: The gear switches to battery supply with mains off and runs until the batteries can no longer supply the lamp. A pass result indicates the battery powered the fitting for the rated period. A full rated duration test is conducted approximately every 52 weeks.

Troubleshooting and error codes

LED INDICATION STATUS COMMENTARY
Permanent Green Everything Working Correctly
Fast Flashing Green (0.1 Sec ON - 0.1 sec OFF) Function Test in Progress
Slow Flashing Green (1 sec ON-1 sec OFF) Duration Test In Progress
Permanent Yellow Load Failure Open Circuit/Short Circuit/LED Failure
Slow Flashing Yellow (1 sec ON-1 sec OFF) Battery Failure Battery Failed Duration or Function Test Battery is Defective/Wrong Battery Voltage
Fast Flashing Yellow (0.1 sec ON-0.1 sec OFF) Charging Failure Incorrect Charging Current
Green and Yellow OFF DC Mode Battery Operation (Emergency Mode)