Manual for ILPH RS 232 / RS 422 - RS 485 ISOLATED

Manual for ILPH RS 232 / RS 422 - RS 485 ISOLATED

Brand: ABB

Category: Other

Document Type: Manual

Language: EN

Available Languages: EN , ES

Uploaded: Nov. 21, 2025, 6:44 p.m.

Manual Publish Date: 2007-03-01

Warranty Information

Warranty information not specified in the document.

1. GENERAL

Interface between an RS 232 serial link and an RS 422 or RS 485 serial link with 500 VDC insulation. Extend transmission distance beyond the 15 m limit of the RS 232 serial link, to cross "noisy" environments, to isolate the 2 systems, to perform multipointing (network) etc.

3.1 POWER SUPPLY

8.5 V to 28 VDC, polarity inversion protection, less than 100 mA power requirement. Galvanic isolation: Power supply / RS 422 - RS 485: 500 VDC. Includes one yellow "power on" LED and a screw-type plug-in connector.

3.2 RS 232 LINK

Complies with EIA RS 232 C/ CCITT V24 / V28. Features over voltage I/O protection. Supports speeds up to 38400 Bauds over 15 m. Galvanic isolation: RS 232 / RS 422 - RS 485: 500 VDC. Includes 3 green LEDs (RxD, TxD, CTRL IN) and screw connection.

3.3 RS 422 - RS 485 LINK

Complies with EIA RS 485 and compatible EIA RS 422 / CCITT V11. Features over voltage I/O protection. Supports speeds up to 38400 Bauds over 1200m. Galvanic isolation: RS 422 - RS 485 / Power supply: 500 VDC, RS 422 - RS 485 / RS 232: 500 VDC. Supports up to 32 receivers simultaneously. Screw connection.

Troubleshooting and error codes

CTRL IN STATUS ACTION ON RS 485
0 logic (+3V ≤ U ≤ +25V) Transmitter active / Receiver inactive
1 logic (-25V ≤ U ≤ -3V) Transmitter inactive / Receiver active
High impedance Transmitter inactive / Receiver active