Manual for RD3M-48

Manual for RD3M-48

Brand: ABB

Category: Safety/Compliance

Document Type: Manual

Language: EN

Available Languages: EN , ES

Uploaded: April 20, 2026, 8:12 p.m.

Manual Publish Date: 2011-09-19

Warranty Information

Refer to the manufacturer for warranty information.

  • The RD3M device provides residual current monitoring and protection.
  • It can be used with MCBs S200 and moulded-case devices in the Tmax range.
  • LEDs and output contacts are used for signalling.
  • Pre-alarm function: Activates by moving the dip-switch to ON. Output contacts 7-8-9 switch if a differential fault above 60% IΔ occurs.
  • Fail-safe function: Incorporated into the device. If the RD3 device loses power, output contacts 10-11-12 will switch.

Troubleshooting and error codes

Signal Condition Output Contacts
ON (green) Stand-by 7-8 NC, 8-9 NO; 10-11 NO, 11-12 NC
Pre Alarm (yellow) Differential fault >60% IΔ 7-8 NO, 8-9 NC; 10-11 NO, 11-12 NC
FAULT (red) Differential fault ≥ IΔtrip 7-8 NO, 8-9 NC; 10-11 NO, 11-12 NC
No power to RD3M FAIL SAFE 7-8 NO, 8-9 NC; 10-11 NO, 11-12 NC
No TR connection FAULT (red) 7-8 NO, 8-9 NC; 10-11 NO, 11-12 NC
Privacy Policy