The Aprilaire Model 800 Canister Steam Humidifier generates steam by energizing electrodes in a water canister. Water is introduced through a fill valve and maintained at a specific level. Steam is then delivered through a dispersion tube into the HVAC system ductwork. The system includes safety features and is controlled by an Automatic Digital Humidifier Control (ADHC) to maintain desired humidity levels.
| Problem | Possible cause | Action |
|---|---|---|
| Humidifier does not energize; steam canister does not heat up, display lights not on | No power to humidifier |
• Check main power supply. Check main line safety switch. • Verify terminal block electrical connections. • Verify humidifier is turned on. |
| No power to low voltage control circuit |
• Check for proper supply voltage. • Verify terminal block electrical connections. • Check for control circuit voltage, 24 VAC. |
|
| Control terminals are open | • Check if auxiliary limit controls are not allowing system to operate, e.g., high limit humidistat, airflow proving switch, etc. Reset, replace, or calibrate as needed. | |
| ADHC faults: • Open, shorted, or incorrect wiring of control |
• Check terminals for 24 VAC. • Check control circuit wiring. |
|
| Steam canister failure | Improper wiring | • Verify proper electrical connections. |
| Mineral buildup on steam canister electrodes | • Inspect steam canister for severe mineral buildup on or around electrodes. If severe mineral buildup is present, replace steam canister. | |
| Steam canister electrode corrosion | • Inspect electrodes for surface corrosion or pitting. This is usually caused by a high chloride level in the supply water. Replace steam canister. | |
| Unit does not fill with water | No water supply to fill valve |
• Verify that manual water supply valve is open and that pressure exists. • Check if in-line strainer in inlet port of fill valve is plugged. Clean strainer or replace. |
| Unit control is not on | • Press On/Off switch. | |
| Malfunctioning fill valve |
• If fill valve does not open: Check for obstruction in valve. - Verify fill valve electrical connections. Verify proper 24 VAC to fill valve. If voltage is present and valve does not open, replace valve. |
|
| Fill valve does not close | Drain valve is open | • Check for obstruction in drain valve. |
| Malfunctioning level control system | • Check that high water sensor electrical plug is fully engaged. | |
| Fill valve is stuck | • Check if there is an obstruction that does not allow valve to seat properly. Clean or replace valve as needed. | |
| Drain valve is open | • Clean or replace drain valve if an obstruction in the valve does not allow complete closure. |