Refer to the service manual for basic features, operation, and servicing.
| Alarm code | Content | Possible cause | |
|---|---|---|---|
| E201 | Pump-down does not end within 60 seconds. | Injection solenoid valve does not close. Coil burned out Coil fell out Leakage of hot gas solenoid valve Defrosting solenoid valve Discharge gas by-pass solenoid valve Low pressure sensor value is abnormal |
Wrong wiring Coil burned out Coil fell out Valve blocked with contamination Valve blocked with contamination Valve blocked with contamination Printed-circuit board malfunction Pressure sensor malfunction |
| E203 | Overcool protection function actuate (control sensor ≤ SP– 3.0) in the chilled ot partial frozen mode for 3 minutes or longer. | Suction modulating valve does not operate. | Lead wire breakage Wrong wiring Coil burned out Adopter PCB is defective |
| Insufficient evaporator fan air flow rate (Only for partial frozen mode) | Valve blocked with contamination Air passage is blocked by foreign materials Evaporator fan damaged |
||
| Evaporator fan motor thermal protector activates | Evaporator fan interferes with guide Lead wire breakage Air passage is blocked by foreign material |
||
| E205 | Abnormal current of evaporator fan motor is detected | Malfunction of wiring Disconnection of lead wire Air passage is blocked by obstacle |
Coil burnt out Damaged bearing |
| E207 | Defrosting time is 90 minutes long | Evaporator outlet sensor gets off from the evaporator outlet tube. Insulation pipe cover of evaporator outlet sensor is improperly installed. Evaporator outlet sensor is defective. |
Lead wire breakage Coil burned out Valve blocked with contamination |
| Defrosting solenoid valve does not open | Lead wire breakage Coil burned out Valve blocked with contamination |
||
| Hot gas solenoid valve does not open. | Lead wire breakage Coil burned out Valve blocked with contamination |
||
| Injection solenoid valve does not open | Lead wire breakage Wrong wiring Coil burned out Coil fell out Valve blocked with contamination |
||
| High-pressure transducer or low-pressure transducer malfunction. Evaporator outlet sensor value is abnormal |
Printed-circuit board malfunction Sensor malfunction |
||
| Excessive frosting | |||
| E303 | Humidity setting request | SRAM (CPU board) malfunction | Resetting |
| E305 | Defrosting interval setting request | ||
| E307 | Calendar setting request | ||
| E311 | Trip start setting request | ||
| E401 | Supply air temperature sensor (SS) malfunction | Line breakage Short circuit Wrong wiring |
Printed-circuit board malfunction |
| E402 | Data recorder supply air temperature sensor (DSS) malfunction | Line breakage Short circuit Wrong wiring |
Printed-circuit board malfunction |
| E403 | Return air temperature sensor (RS) malfunction | Line breakage Short circuit Wrong wiring |
CPU board malfunction |
| E404 | Data recorder return air temperature sensor (DRS) malfunction | Line breakage Short circuit Wrong wiring |
CPU board malfunction |
| E405 | Discharge temperature sensor (DCHS) malfunction | Line breakage Short circuit Wrong wiring |
CPU board malfunction |