Manual for LXE10E-1E

Manual for LXE10E-1E

Brand: DAIKIN

Category: Refrigeration Unit

Document Type: Manual

Language: EN

Available Languages: EN , ES

Uploaded: Sept. 12, 2025, 4:27 a.m.

Warranty Information

Refer to the service manual for basic features, operation, and servicing.

  • The unit has two main operation modes: cargo cooling control mode and unit inspection mode.
  • The cargo cooling control mode includes Frozen mode, Chilled mode, and Defrosting mode.
  • Frozen mode: Compressor ON/OFF control based on return air temperature.
  • Chilled mode: Capacity control with suction modulating valve and hot-gas bypass control.
  • Defrosting mode: Hot-gas defrosting with refrigerant metering control.

Troubleshooting and error codes

Alarm code Content Possible cause
E201 Pump-down does not end within 60 seconds. Injection solenoid valve does not close.
Coil burned out
Coil fell out
Leakage of hot gas solenoid valve
Defrosting solenoid valve
Discharge gas by-pass solenoid valve
Low pressure sensor value is abnormal
Wrong wiring
Coil burned out
Coil fell out
Valve blocked with contamination
Valve blocked with contamination
Valve blocked with contamination
Printed-circuit board malfunction
Pressure sensor malfunction
E203 Overcool protection function actuate (control sensor ≤ SP– 3.0) in the chilled ot partial frozen mode for 3 minutes or longer. Suction modulating valve does not operate. Lead wire breakage
Wrong wiring
Coil burned out
Adopter PCB is defective
Insufficient evaporator fan air flow rate (Only for partial frozen mode) Valve blocked with contamination
Air passage is blocked by foreign materials
Evaporator fan damaged
Evaporator fan motor thermal protector activates Evaporator fan interferes with guide
Lead wire breakage
Air passage is blocked by foreign material
E205 Abnormal current of evaporator fan motor is detected Malfunction of wiring
Disconnection of lead wire
Air passage is blocked by obstacle
Coil burnt out
Damaged bearing
E207 Defrosting time is 90 minutes long Evaporator outlet sensor gets off from the evaporator outlet tube.
Insulation pipe cover of evaporator outlet sensor is improperly installed.
Evaporator outlet sensor is defective.
Lead wire breakage
Coil burned out
Valve blocked with contamination
Defrosting solenoid valve does not open Lead wire breakage
Coil burned out
Valve blocked with contamination
Hot gas solenoid valve does not open. Lead wire breakage
Coil burned out
Valve blocked with contamination
Injection solenoid valve does not open Lead wire breakage
Wrong wiring
Coil burned out
Coil fell out
Valve blocked with contamination
High-pressure transducer or low-pressure transducer malfunction.
Evaporator outlet sensor value is abnormal
Printed-circuit board malfunction
Sensor malfunction
Excessive frosting
E303 Humidity setting request SRAM (CPU board) malfunction Resetting
E305 Defrosting interval setting request
E307 Calendar setting request
E311 Trip start setting request
E401 Supply air temperature sensor (SS) malfunction Line breakage
Short circuit
Wrong wiring
Printed-circuit board malfunction
E402 Data recorder supply air temperature sensor (DSS) malfunction Line breakage
Short circuit
Wrong wiring
Printed-circuit board malfunction
E403 Return air temperature sensor (RS) malfunction Line breakage
Short circuit
Wrong wiring
CPU board malfunction
E404 Data recorder return air temperature sensor (DRS) malfunction Line breakage
Short circuit
Wrong wiring
CPU board malfunction
E405 Discharge temperature sensor (DCHS) malfunction Line breakage
Short circuit
Wrong wiring
CPU board malfunction