Manual for LXE10E-A31

Manual for LXE10E-A31

Brand: DAIKIN

Category: Refrigeration Unit

Document Type: Manual

Language: EN

Available Languages: EN , ES

Uploaded: Sept. 12, 2025, 4:14 a.m.

Warranty Information

No specific warranty period is mentioned in this section.

Operation Modes and Control

The unit has several operation modes: Frozen, Partial frozen, Chilled, and Defrosting. Each mode has a specific setting temperature range and utilizes different control sensors (Return air temperature sensor or Supply air temperature sensor) to manage operation. For instance, the Frozen mode uses the Return air temperature sensor for Compressor ON/OFF control, while the Chilled mode uses the Supply air temperature sensor for Capacity control operation with suction modulating valve and hot-gas bypass control.

Dehumidification Mode

Dehumidification is controlled by a reheat coil. To activate it, controller settings are required. The Reheat Solenoid Valve (RSV) opens, and the "DEHUMID" LED lamp will light up. The dehumidification range can be set from 60%RH to 95%RH.

Mode Operation

In mode operation, the following settings/operations are available:

  1. Generator setting: Reduces total power consumption to a desired maximum setting for specific generators or power facilities. Selections include "off (No limit)" and various KVA ratings.
  2. Automatic pump down: Can be executed automatically.
  3. Dehumidification mode setting: When "Dehumidification" is set to "on", the inside humidity can be adjusted from 95% to 50% RH.

Troubleshooting and error codes

Alarm grouping Alarm code Alarm content Action with alarm
Permanent stop F101 HPS activated within 30 seconds after operation start or protection device activated 5 times at start-up operation or Fuse 1 brown (Refer Page 7-7). Unit stops
F109 Low- pressure drops to-85kPa or lower within 2 seconds after operation start. Unit stops
F111 HPS does not activate when it reaches to the set value. Unit stops
F301 Temperature setting required (SRAM failure) Unit stops
F401 Return/Supply air sensor malfunction (at chilled mode) Unit stops
F403 Return/Supply air sensor malfunction (at partial frozen mode) Unit stops
F603 Suction modulating valve (SMV) does not fully close contrary to the designation or initial setting of the controller is wrong. Unit stops
Control error E101 High-pressure switch activated during normal operation. Restart after 3-minute
E103 CTP or electronic OC activated during normal operation. Restart after 3-minute
E105 Micro processor OC activated during normal operation. Restart after 3-minute
E107 DCHS became abnormal high temperature during operation. Restart after 3-minute
Printed-circuit board failure E201 Low pressure drops to-90kPa or lower for 2 seconds or longer successively during normal operaton. Restart after 3-minute
E203 Overcool protection activates in the chilled or partial frozen mode. (Control temperature ≤ SP-3°C or for 3 minutes) Restart after 3-minutes
Sensor alarm E401 Supply air temperature sensor (SS) malfunction Back-up operation
E402 Data recorder supply air temperature sensor (DSS) malfunction Back-up operation
E403 Return air temperature sensor (RS) malfunction Back-up operation
E404 Data recorder return air temperature sensor (DRS) malfunction Back-up operation
E405 Discharge air temperature sensor (DCHS) malfunction Only alarm display
E406 Suction gas temperature sensor (SGS) malfunction Back-up operation
E407 Evaporator inlet temperature sensor (EIS) malfunction Back-up operation
E409 Evaporator outlet sensor (EOS) malfunction Back-up operation
E411 Ambient sensor (AMBS) malfunction Only alarm display
E413 Low pressure transducer (LPT) malfunction Back-up operation
E415 High pressure transducer (HPT) malfunction Back-up operation
E417 Voltage sensor (PT1) malfunction Only alarm display