Warranty Information

No specific warranty period is mentioned in this manual.

The unit has several operation modes: Frozen mode, Chilled mode, and Defrosting mode.

Frozen mode: Compressor ON/OFF control based on return air temperature.

Chilled mode: Capacity control with suction modulating valve and hot-gas bypass control, based on supply air temperature.

Defrosting mode: Hot-gas defrosting with refrigerant metering control.

The unit also supports dehumidification control via a reheat coil, adjustable from 60-95%RH. Mode operation allows for generator setting, automatic pump down, and dehumidification mode setting.

Troubleshooting and error codes

Alarm grouping Alarm code Alarm content Action with alarm
Permanent stop F101 HPS activated within 30 seconds after operation start or protection device activated 5 times at start-up operation or Fuse 1 brown (Refer Page 7-7). Unit stops
F109 Low- pressure drops to–85kPa or lower within 2 seconds after operation start. Unit stops
F111 HPS does not activate when it reaches to the set value. Unit stops
F301 Temperature setting required (SRAM failure) Unit stops
F401 Return / Supply for data / Supply air sensor malfunction (at chilled mode) Unit stops
F603 Suction modulating valve (SMV) does not fully close contrary to the designation or initial setting of the controller is wrong. Unit stops
Protection device activation F701 Abnormal high voltage (over 600V) or low voltage (under 300V) Unit stops
F705 S phase became open phase Unit stops
F803 Abnormalities, which make it impossible to continue operation (Note2.) Unit stops
Control error E101 High-pressure switch activated during normal operation. Restart after 3-minute
E103 CTP or electronic OC activated during normal operation. Restart after 3-minute
E105 Micro processor OC activated during normal operation. Restart after 3-minute
E107 DCHS became abnormal high temperature during operation. Restart after 3-minute
E109 In the event the refrigerant circulation rate is low, the unit error will be detected to stop the unit. Low pressure drops to-90kPa or lower for 2 seconds or longer successively during normal operaton. If this error occurs two times, F803 will stand by for three minutes to restart then. Restart after 3-minute
E201 Pump down is not completed within 90 seconds. Only alarm display
E203 Overcool protection activates in the chilled. (Control temperature ≤ SP-3°C or for 3 minutes) Restart after 3-minutes
E205 Evaporator for motor failure (Note 2) Only alarm display
E207 Defrosting is not completed within 90 minutes Only alarm display
E303 Humidity setting required (SRAM failure) Only alarm display
E305 Defrost timer setting required (SRAM failure) Only alarm display