Front Panel Commands

  • SET: Display or change target set point; select parameter or confirm operation; start manual defrost.
  • UP/DOWN Arrows: Browse parameter codes or adjust values.

Key Combinations

  • + keys: Lock/unlock keyboard.
  • SET + Up Arrow: Enter programming mode.
  • SET + Down Arrow: Exit programming mode.

LED Indicators

  • Indicate compressor status, defrost, fan operation, measurement unit, and programming mode.

Basic Operations

  • View Set Point: Press SET key.
  • Change Set Point: Press and hold SET for 3s, adjust with arrows, press SET to confirm.
  • Start Manual Defrost: Press DEF key for at least 4s.
  • Change Parameter Value: Enter programming mode (SET + Up Arrow), select parameter, press SET to view value, adjust with arrows, press SET to save.

Troubleshooting and error codes

MESSAGGIO CAUSA USCITE
"P1" Sonda termostato guasta Uscita compressore secondo parametri "Cy" e "Cn"
"P2" Sonda evaporatore guasta Sbrinamento a tempo
"HA" Allarme di alta temperatura Non modificata
"LA" Allarme bassa temperatura Non modificata
"EA" Allarme esterno Non modificate
"CA" Allarme di blocco pressostato Carichi spenti
"dA" Porta aperta Carichi secondo "dC"