| Page | Issue | Solution |
|---|---|---|
| 19 | Test the sounders (local and loop) | Press the Evacuate key, then Silence/Resound and Reset keys. Be aware of nuisance alarms. |
| 19 | Test the open circuit monitoring | Disconnect EOL resistors, ensure panel reports faults, then restore system. |
| 19 | Test the short circuit monitoring | Replace EOL resistors with short circuits, ensure panel reports faults, then restore system. |
| 17, 18 | Auto addressing procedure | Ensures devices are accessible by the panel. Requires loop wiring troubles to be removed. Only effective if NG1 devices are present. Device mapping only after double address faults are removed. |
| 35 | Error codes | Refer to the "EXPECTED OPTIONS" and "EN 54-2 ESSENTIAL CHARACTERISTICS" sections for expected behaviors and passed tests. Specific error codes are not listed in this excerpt. |