Brand: GE
Category: Other
Document Type: Manual
Language: EN
Available Languages: EN , ES
Uploaded: Nov. 21, 2025, 6:22 p.m.
This limited warranty covers defects in materials or workmanship for two years, including labor and related service.
1. Power Off: The air conditioner is off.
2. Air Conditioning Modes: Compressor and fans run to provide cold air. Three modes correspond to low, medium, and high fan speeds.
3. Fan Only Modes: Fans circulate air. Three modes correspond to low, medium, and high fan speeds.
4. Temperature Selection: Adjusts the room set point temperature to control cooling.
Use the lever on the control panel to open/close the vent. Adjust the 4 side ports for airflow.
Droplets of water hitting the condenser (pinging/clicking), air movement from the fan, clicks from control cycling, and hum/pulsating noise from the compressor.
| Problem | Possible Cause | What To Do |
|---|---|---|
| Air Conditioner does not operate | An RV fuse has blown, or circuit breaker has tripped. | Replace the fuse or reset the circuit breaker. If the problem continues, call an electrician. See "Electrical Requirements." |
| The mode setting is in the OFF position. | Press POWER or turn the Mode control to an active setting. | |
| The local power has failed. | Wait for power to be restored. | |
| Air conditioner blows fuses or trips circuit breakers | Too many appliances are being used on the same circuit. | Unplug or relocate appliances that share the same circuit. |
| Time-delay fuse or circuit breaker of the wrong capacity is being used. | Replace with a time-delay fuse or circuit breaker of the correct capacity. See "Electrical Requirements." | |
| Air conditioner seems to run too much | You are trying to restart the air conditioner too soon after turning off the air conditioner. | Wait at least 3 minutes after turning off the air conditioner before trying to restart the air conditioner. |
| The air conditioner is in a heavily occupied room, or heat-producing appliances are in use in the room. | Use exhaust vent fans while cooking or bathing and try not to use heat-producing appliances during the hottest part of the day. A higher capacity air conditioner may be required depending on the size of the room being cooled. | |
| The air conditioner is not properly sized for your RV. | Check the cooling capabilities of your RV air conditioner. | |
| Air conditioner cycles on and off too much or does not cool room in cooling mode | The filter is dirty or obstructed by debris. | Clean the filter. |
| There is excessive heat or moisture (open container cooking, showers, etc.) in the room. | Use a fan to exhaust heat or moisture from the room. Try not to use heat-producing appliances during the hottest part of the day. | |
| The louvers or ducts are closed. | Make sure louvers are open. | |
| The outside temperature is below 60°F (15°C). | Do not try to operate your air conditioner in the cooling mode when the outside temperature is below 60°F (15°C). | |
| The temperature of the room you are trying to cool is extremely hot. | Allow extra time for the air conditioner to cool off a very hot room. | |
| Windows or doors to the outside are open. | Close all windows and doors. | |
| The Temperature control is not at a cool enough setting. | Adjust the TEMP control to a cooler setting by pressing the minus button to reduce the temperature. Set the Fan Speed control to the highest setting. | |
| Wall thermostat improperly installed | Verify proper installation of Wall Thermostat per installation instructions (pg. 5...not on exterior wall or in direct sunlight......in an area affected by a vent or duct...) | |
| Water drips from cabinet into your house | The indoor coil may be frozen. | De-ice by running the fan only until clear. |
| The air conditioner's mounting gasket may not be sealed against the roof. | Check mounting bolts and tighten to 45 ± 5 in-lbs if necessary. |