Manual for ARC13AAC

Manual for ARC13AAC

Brand: GE

Category: Other

Document Type: Manual

Language: EN

Available Languages: EN , ES

Uploaded: Nov. 21, 2025, 6:22 p.m.

Warranty Information

This limited warranty covers defects in materials or workmanship for two years, including labor and related service.

Controls

1. Power Off: The air conditioner is off.

2. Air Conditioning Modes: Compressor and fans run to provide cold air. Three modes correspond to low, medium, and high fan speeds.

3. Fan Only Modes: Fans circulate air. Three modes correspond to low, medium, and high fan speeds.

4. Temperature Selection: Adjusts the room set point temperature to control cooling.

Air Direction

Use the lever on the control panel to open/close the vent. Adjust the 4 side ports for airflow.

Normal Operating Sounds

Droplets of water hitting the condenser (pinging/clicking), air movement from the fan, clicks from control cycling, and hum/pulsating noise from the compressor.

Troubleshooting and error codes

Problem Possible Cause What To Do
Air Conditioner does not operate An RV fuse has blown, or circuit breaker has tripped. Replace the fuse or reset the circuit breaker. If the problem continues, call an electrician. See "Electrical Requirements."
The mode setting is in the OFF position. Press POWER or turn the Mode control to an active setting.
The local power has failed. Wait for power to be restored.
Air conditioner blows fuses or trips circuit breakers Too many appliances are being used on the same circuit. Unplug or relocate appliances that share the same circuit.
Time-delay fuse or circuit breaker of the wrong capacity is being used. Replace with a time-delay fuse or circuit breaker of the correct capacity. See "Electrical Requirements."
Air conditioner seems to run too much You are trying to restart the air conditioner too soon after turning off the air conditioner. Wait at least 3 minutes after turning off the air conditioner before trying to restart the air conditioner.
The air conditioner is in a heavily occupied room, or heat-producing appliances are in use in the room. Use exhaust vent fans while cooking or bathing and try not to use heat-producing appliances during the hottest part of the day. A higher capacity air conditioner may be required depending on the size of the room being cooled.
The air conditioner is not properly sized for your RV. Check the cooling capabilities of your RV air conditioner.
Air conditioner cycles on and off too much or does not cool room in cooling mode The filter is dirty or obstructed by debris. Clean the filter.
There is excessive heat or moisture (open container cooking, showers, etc.) in the room. Use a fan to exhaust heat or moisture from the room. Try not to use heat-producing appliances during the hottest part of the day.
The louvers or ducts are closed. Make sure louvers are open.
The outside temperature is below 60°F (15°C). Do not try to operate your air conditioner in the cooling mode when the outside temperature is below 60°F (15°C).
The temperature of the room you are trying to cool is extremely hot. Allow extra time for the air conditioner to cool off a very hot room.
Windows or doors to the outside are open. Close all windows and doors.
The Temperature control is not at a cool enough setting. Adjust the TEMP control to a cooler setting by pressing the minus button to reduce the temperature. Set the Fan Speed control to the highest setting.
Wall thermostat improperly installed Verify proper installation of Wall Thermostat per installation instructions (pg. 5...not on exterior wall or in direct sunlight......in an area affected by a vent or duct...)
Water drips from cabinet into your house The indoor coil may be frozen. De-ice by running the fan only until clear.
The air conditioner's mounting gasket may not be sealed against the roof. Check mounting bolts and tighten to 45 ± 5 in-lbs if necessary.
Privacy Policy