The FSXN series belongs to the SET FREE series, characterized by its modular design. It offers refrigeration, heating, or both simultaneously, for personalized environments. The units are designed with environment-friendly R410A gas refrigerant and adhere to RoHS and Green Dot standards. This manual covers installation, piping, electrical wiring, control systems, optional functions, test runs, troubleshooting, spare parts, servicing, electrical checks, and maintenance notes for the FSXN series outdoor units and associated CH units.

Troubleshooting and error codes

No. Check item Action Judgement
1 Is the service space sufficient? Yes No
2 Is there a short circuit in the discharge air? Yes No
3 Any heat influence? Yes No
4 Is the earth wire connected? Yes No
5 Refrigerant pipe Correct Incorrect
6 Fixing of units Correct Incorrect
7 Are the internal and external surfaces damaged? Yes No
8 Are the screws and bolts tightened? Tighten if loose. Tightened Not tightened
9 Are the terminal screws tightened? Tighten the screws on the terminals with a Philips screwdriver. Tightened Not tightened
10 Are the compressor terminals tightened? Push all the terminals. Push Not push
11 Insulation resistance Measure the insulation resistance with a multimeter. Fan and compressor: Motor: greater than 3 MΩ. Others: greater than 3 MΩ. Correct Incorrect
12 Are there drainage problems in the water flow? Check the smoth flow with a little water. Correct Incorrect
13 Is there leakage in the compressor? Check there is no leakage. Correct Incorrect
14 Is there leakage in the outdoor heat exchanger? Check there is no leakage. Correct Incorrect
15 Is there leakage in the indoor heat exchanger? Check there is no leakage. Correct Incorrect
16 Is there leakage in the 4-way valves? Check there is no leakage. Correct Incorrect
17 Is there leakage in the check valve? Check there is no leakage. Correct Incorrect
18 Is there leakage in the accumulator? Check there is no leakage. Correct Incorrect
19 Is there leakage in the strainer? Check there is no leakage. Correct Incorrect
20 Is there leakage in the expansion valve? Check there is no leakage. Correct Incorrect
21 Is there leakage in the piping? Check there is no leakage. Correct Incorrect
22 Check the direction of the fans See the air flow volume. Correct Incorrect
23 Check the voltage of each phase Greater than 220 V. Correct Incorrect
24 Vibrations and noise Check the compressor, the piping, the fan, etc. Correct Incorrect
25 Activation of the operation modes Activate the COOL switch, the HEAT switch, the STOP switch and the TEMP switch. Correct Incorrect
26 Cut-out of the high pressure switch Check the current activation valve. Correct Incorrect
27 Activate the drain-up mechanism Check it is activated during cooling mode. Correct Incorrect
28 Indoor inlet air temperature DB/WB (°C) DB (°C) WB
29 Indoor outlet air temperature DB/WB (°C) DB (°C) WB
30 Outdoor inlet air temperature DB/WB (°C) DB (°C) WB
31 Outdoor outlet air temperature DB/WB (°C) DB (°C) WB
32 High pressure switch MPaG
33 Low pressure switch MPaG
34 Operating voltage V
35 Operating current A
36 Instructions for the customer for cleaning the filters Done Not yet
37 Instructions for the customer for the cleaning procedure Done Not yet
38 Instructions for the customer for operation Done Not yet