Brand: HITACHI
Category: Air Conditioner
Document Type: Manual
Language: EN
Available Languages: EN , ES
Brand: HITACHI
Category: Air Conditioner
Document Type: Manual
Language: EN
Available Languages: EN , ES
Uploaded: Nov. 21, 2025, 8:36 p.m.
Manual Publish Date: 2011-08-01
Warranty information is not explicitly stated in the provided manual sections.
| No. | Check item | Action | Judgement | |
|---|---|---|---|---|
| 1 | Is the service area sufficient? | — | Yes | No |
| 2 | Is there a short circuit of the discharged air? | — | Yes | No |
| 3 | Any heat influence? | — | Yes | No |
| 4 | Is the ground wire connected? | — | Yes | No |
| 5 | Refrigerant piping. | — | Good | Not Good |
| 6 | Fixing the units. | — | Good | Not Good |
| 7 | Is there any damage on the outer surface or the internal surface? | Yes | No | — |
| 8 | Checking the screw and the bolts. | Tighten if loosened. | Tightened | Not Tightened |
| 9 | Tightening the terminal screws. | Tighten all the terminal screws with a Phillips screwdriver. | Tightened | Not Tightened |
| 10 | Are the compressor terminals tightly fixed? | Push all the terminals. | Pushed | Not Pushed |
| 11 | Insulation resistance. | Measure the insulation resistance with an insulation resistance meter. Comp. and fan. motor: greater than 3ΜΩ. Others: greater than 3ΜΩ. | Good | Not Good |
| 12 | Does the drain water flow smoothly? | Check the smooth flow by pouring some water. | Good | Not Good |
| 13 | Check for a leakage in the compressor. | Check for any leakage. | Good | Not Good |
| 14 | Check for a leakage in the outdoor heat exchanger. | ditto | Good | Not Good |
| 15 | Check for a leakage in the indoor heat exchanger. | ditto | Good | Not Good |
| 16 | Check for a leakage in the 4-way valve. | ditto | Good | Not Good |
| 17 | Check for a leakage in the check valve. | ditto | Good | No Good |
| 18 | Check for a leakage in the accumulator. | ditto | Good | Not Good |
| 19 | Check for a leakage in the strainer. | ditto | Good | Not Good |
| 20 | Check for a leakage in the electronic expansion valve | ditto | Good | Not Good |
| 21 | Check for a leakage in the piping. | ditto | Good | Not Good |
| 22 | Check the direction of the fans. | By viewing the airflow volume. | Good | Not Good |
| 23 | Voltage among each phase. | Higher than AC220V. | Good | Not Good |
| 24 | Vibration and sound. | Check the fan the compressor the piping and others. | Good | Not Good |
| 25 | Activation of each operation mode. | Check the activation of the COOL switch the HEAT switch the STOP switch and the TEMP switch. | Good | Not Good |
| 26 | High-pressure cut-out switch. | Check the actual activation value. | Good | Not Good |
| 27 | Check the activation of the drain-up mechanism. | Check the activation during the cooling process. | Good | Not Good |
| 28 | Air inlet temperature of the indoor unit DB/WB. | — | (°C)DB | (°C)WB |
| 29 | Air outlet temperature of the indoor unit DB/ WB. | — | (°C)DB | (°C)WB |
| 30 | Air inlet temperature of the outdoor unit DB/ WB. | — | (°C)DB | (°C)WB |
| 31 | Air outlet temperature of the outdoor unit DB/ WB. | — | (°C)DB | (°C)WB |
| 32 | High-pressure switch. | — | kg/cm²G | — |
| 33 | Low-pressure switch. | — | kg/cm²G | — |
| 34 | Operating voltage. | — | V | — |
| 35 | Operating current. | — | A | — |
| 36 | Instructions to the client for cleaning the air filter. | Done | Not yet | — |
| 37 | Instructions to the client about the cleaning method. | Done | Not yet | — |
| 38 | Instructions to the client about the operation. | Done | Not yet | — |