YUTAKI units produce heating and domestic hot water, transforming renewable energy from the outside air into heat. They extract free energy from the air, enough to heat a home even on the coldest winter day. Every kW of electricity used can yield up to more than 5 kW of energy for heating, providing savings of up to 80% compared to traditional fossil fuel boilers. The new YUTAKI series offers outstanding performance in space heating and domestic hot water production. Cooling operation is also possible with a dedicated accessory. The system is controlled by a new user controller (PC-ARFHE) with enhanced functions.
The YUTAKI system can be configured for:
| Alarm Code | Retry Stop Code | Yutaki S/SC | Yutaki S80 | Yutaki M | Origin | Detail of Abnormality | Main Factors |
|---|---|---|---|---|---|---|---|
| 3 | - | 0 | 0 | 0 | Communication | Transmission Alarm (Not outdoor unit detected) | Loose, disconnected, broken or short-circuited connector |
| 11 | - | 0 | 0 | 0 | Indoor | Water inlet thermistor abnormally (THMwi) | Loose, disconnected, broken or short-circuited connector |
| 12 | - | 0 | 0 | 0 | Indoor | Water outlet thermistor abnormally (THMwo) | Loose, disconnected, broken or short-circuited connector |
| 13 | - | 0 | 0 | 0 | Indoor | Indoor Liquid Pipe Temp Thermistor Abnormality (THMI) | Loose, disconnected, broken or short-circuited connector |
| 14 | - | 0 | 0 | 0 | Indoor | Indoor Gas Pipe Temperature Thermistor Abnormality (THMg) | Loose, disconnected, broken or short-circuited connector |
| 15 | - | (0) | (0) | (0) | Indoor | Water Circuit 2 thermistor abnormally (THMwo2) | Loose, disconnected, broken or short-circuited connector |
| 16 | - | (0) | (0) | (0) | Indoor | Water DHW thermistor abnormally (THMdhwt) | Loose, disconnected, broken or short-circuited connector |
| 17 | - | (0) | (0) | (0) | Indoor | Auxiliary sensor 2 thermistor abnormally (THMaux2) | Loose, disconnected, broken or short-circuited connector |
| 18 | - | (0) | (0) | (0) | Indoor | Auxiliary sensor 1 thermistor abnormally (THMaux1) | Loose, disconnected, broken or short-circuited connector |
| 19 | - | 0 | - | - | Indoor | Water Plate HEX pipe thermistor abnormally (THMwohp) | Loose, disconnected, broken or short-circuited connector |
| 23 | - | 0 | - | - | Indoor | Suction R134a pipe thermistor abnormally (THMs) | Loose, disconnected, broken or short-circuited connector |
| 25 | - | (0) | (0) | (0) | Indoor | Discharge R134a pipe thermistor abnormally (THMd) | Loose, disconnected, broken or short-circuited connector |
| 40 | - | 0 | 0 | 0 | Indoor | Incorrect LCD setting | Current LCD configuration does not allow proper operation |
| 63 | - | (0) | (0) | (0) | Communication | Transmission error between Central and indoor communication | Indoor fuse meltdown, Indoor/ central connection wiring (breaking, wiring error, etc.) |
| 70 | P70 | 0 | 0 | 0 | Indoor | Hydraulic alarm flow & Water Pump malfunction | Water flow is not detected in the hydraulic cycle or Pump defective |
| 83 | P83 | 0 | 0 | 0 | Indoor | Hydraulic alarm pressure | Water pressure is not detected in the hydraulic cycle |
| 72 | - | 0 | - | - | Indoor | Thermostat Heater Alarm | High temperature is detected in Electric Heater |
| 73 | - | 0 | 0 | 0 | Indoor | Mixing over-temperature limit protection for Mixed circuit. | Circuit 2 supply temperature > Target temperature + offset |
| 74 | P74 | 0 | 0 | 0 | Indoor | Unit over-temperature limit protection | Two > Tmax +5K |