| LED | Status | Description |
|---|---|---|
| LED1 green | Solid | Mains voltage (230 V AC) is switched on. Device is ready for operation. |
| LED1 green | Blinking | 230 V AC mains voltage failure. External devices are supplied by connected batteries (emergency operation). |
| LED1 red | Solid | Battery internal resistance too high (after a battery test). Deep discharge warning (UBat. < 22 V). |