Manufacturer warrants products for 36 months from the date of manufacture against defects in material and workmanship.
| Trouble Condition | Possible Cause | Remedy |
|---|---|---|
| Low AC Power | No AC power to GFPS-9 | Check AC power source, fuses, and wiring. |
| Low Battery | Batteries are discharged or faulty. | Check battery connections, charge batteries, or replace if necessary. |
| Earth Fault | Ground fault to system power or ground. | Check wiring for ground faults and correct as needed. |
| Output Trouble | EOL supervision trouble or power-limited condition at an output. | Check output wiring, EOL resistor, and connected devices for faults or overloads. |
| Input Trouble | Trouble condition on the input circuit from the control panel. | Check wiring from the control panel to the GFPS-9 inputs. |