| No. | Check Item |
|---|---|
| 1 | If the input or output system is changed, ensure that the short-circuit copper bar status and cable connections at input and output ports are correct. |
| 2 | The phase sequence of the input power is correct. Use a multimeter to check that the input and output are not short-circuited. |
| 3 | Cables and terminals are securely connected. |
| 4 | Battery cables and terminals are connected correctly, and voltages comply with industry standards. |
| 5 | The UPS is properly connected to the lithium battery string. |
| 6 | Input circuit breakers and load circuit breakers are OFF. |
| 7 | Power cables and signal cables are correctly identified. |
| 8 | The ground cable is reliably connected. The voltage difference between the neutral wire and the ground cable is less than 5 V AC. |
| 9 | The build-out resistor is correctly installed. |
| 10 | The voltage range of the UPS upstream input circuit breaker is 80-280 V AC (phase voltage), and the rated frequency is 50 Hz/60 Hz. |
| 11 | The positive and negative voltages of the lithium battery measured by a multimeter ranges from 41 V to 51 V. |