| Error No. | Error Type | Error Point | Main Reasons |
| 52 | Transmission error between (Inverter PCB → Main PCB) | Main controller can't receive signal from inverter controller | 1. Power cable or transmission cable is not connected 2. Defect of outdoor Main fuse/Noise Filter 3. Defect of outdoor Main / inverter PCB |
| 53 | Transmission error (Indoor unit → Main PCB) | In case Main PCB can't receive signal from indoor unit | 1. Transmission cables are not connected 2. Transmission cables are short / open 3. Defect of outdoor Main / indoor PCB |
| 60 | Inverter PCB EEPROM error | EEPROM Access error and Check SUM error | 1. EEPROM contact defect/wrong insertion 2. Different EEPROM Version 3. ODU inverter PCB assembly damage |
| 62 | Heatsink High error | Inverter PCB heatsink temperature is over 95°C(203°F) | 1. Overload operation (Pipe clogging/ Covering/EEV defect/Ref. overcharge) 2. ODU fan locking 3. Heatsink assembly of INV PCB assemble condition abnormal 4. Defect of temperature sensing circuit part defect of INV PCB |
| 65 | Heatsink High error | Inverter PCB heatsink sensor is open or short | 1. Heatsink assembly of INV PCB assemble condition abnormal 2. Defect of temperature sensing circuit part defect of INV PCB |
| 67 | Fan Lock Error | Fan RPM is 10RPM or less for 5 sec. when ODU fan starts or 40 RPM or less after fan starting. | 1. Fan motor defect / assembly condition abnormal 2. Wrong connection of fan motor connector 3. Reversing rotation after RPM target apply 4. Inverter PCB assembly defect |
| 73 | AC input instant over current error (Matter of software) | Inverter PCB input power current is over 48A(peak) for 2ms | 1. Overload operation (Pipe clogging/Covering/EEV defect/Ref. overcharge) 2. Compressor damage(Insulation damage/Motor damage) 3. Input voltage abnormal (L1,L2) 4. Power line assemble condition abnormal 5. Inverter PCB assembly damage(input current sensing part) |
| 86 | Main PCB EEPROM Error | EEPROM Access Error | 1. No EEPROM 2. EEPROM wrong insertion |
| 113 | Outdoor unit liquid pipe (condenser) temperature sensor error | Abnormal sensor resistance value (Open/Short) | 1. Defective temperature sensor connection 2. Defective temperature sensor (Open / Short) 3. Defective outdoor unit PCB |
| 114 | Outdoor unit sub-cooling inlet / outlet temperature sensor error | Abnormal sensor resistance value (Open/Short) | 1. Defective temperature sensor connecter connection 2. Defective temperature sensor (Open/Short) 3. Defective outdoor PCB |
| 151 | Function error of outdoor 4way (reversing valve) | Function error of 4way (reversing valve) in Main | 1. Wrong operation of 4way valve because of sludge etc. inflow 2. No pressure difference because of compressor fault 3. Wrong installation of In/outdoor common pipe 4. Defect of 4way valve |