Manual for R32

Manual for R32

Brand: Panasonic

Category: Air Conditioner

Document Type: Manual

Language: EN

Available Languages: EN , ES

Uploaded: Nov. 21, 2025, 7:50 p.m.

Warranty Information

Refer to the warranty information provided by the sales dealer or installer.

Basic Operation

  • Cooling Mode: Set the desired temperature to cool the room.
  • Heating Mode: Set the desired temperature to heat the room.
  • Fan Mode: Operates the fan without heating or cooling.
  • Auto Mode: The unit automatically selects between cooling and heating to maintain the set temperature.
  • Dehumidify Mode: Reduces humidity in the room.
  • Remote Controller Functions: Allows selection of modes, temperature, fan speed, timer settings, and other advanced features like auto-address setting.
  • Auto Address Setting: Automatically assigns addresses to indoor and outdoor units for system operation.
  • Test Run: Performed after installation to confirm proper operation.

Troubleshooting and error codes

Self-Diagnostic Functions and Corrections

Abnormal Display Alarm Contents Error Location
E01 Faulty remote controller Replace the remote controller
E02 Disconnection / Contact failure of remote controller wiring Correct the remote controller wiring
E03 CHK (check) pins on the indoor unit control PCB are short circuited Remove the short
E04 Non-group control: Power supply OFF of outdoor unit. Disconnection / Contact failure of inter-unit wiring. Group control: Automatic address operation was not carried out. Execute auto address setting
E06 Disconnection / Contact failure of inter-unit wiring. Communication circuit fuse (F302) on indoor unit control PCB opened. Correct the inter-unit control wiring. Check the electrical connection of fuse (F302) on indoor unit control PCB.
E12 Indoor unit control PCB address settings error. Auto address setting start is prohibited. Indoor unit address re-setting. Check the inter-unit control wiring.
E14 Duplication of main unit in group control. Check the indoor unit combination.
E15 The total capacity of indoor units are too low/high. Check the inter-unit wiring. Check the indoor and outdoor unit control PCB.
E16 The number of indoor units is two or more. No indoor unit connected. Check the inter-unit wiring. Check the indoor and outdoor unit control PCB.
E20 Outdoor unit communication error. Check the outdoor unit control PCB.
E24 Outdoor unit communication error. Check the outdoor unit control PCB.
E29 Compressor discharge temperature sensor (TD) trouble. Check the compressor discharge temperature sensor (TD). Check the outdoor unit control PCB.
F04 Outdoor heat exchanger temperature sensor (C1) trouble. Check the outdoor unit heat exchanger temperature sensor (C1). Check the outdoor unit control PCB.
F06 Outdoor heat exchanger temperature sensor (C1) trouble. Check the outdoor unit heat exchanger temperature sensor (C1). Check the outdoor unit control PCB.
F07 Outdoor heat exchanger temperature sensor (C2) trouble. Check the outdoor unit heat exchanger temperature sensor (C2). Check the outdoor unit control PCB.
F08 Outdoor air temperature sensor (TO) trouble. Check the outdoor air temperature sensor (TO). Check the outdoor unit control PCB.
F10 Compressor suction temperature sensor (TS) trouble. Check the compressor suction temperature sensor (TS). Check the outdoor unit control PCB.
F12 Outdoor unit EEPROM trouble. Check the outdoor unit EEPROM. Check the outdoor unit control PCB.
F29 Outdoor unit EEPROM trouble. Check the outdoor unit EEPROM. Check the outdoor unit control PCB.
F31 Outdoor unit EEPROM trouble. Check the outdoor unit EEPROM. Check the outdoor unit control PCB.
H01 Primary (input) overcurrent detected. Check the refrigerant cycle (abnormal overload operation). Check the outdoor unit control PCB.
H02 PAM trouble. Primary current CT sensor failure. Check the outdoor unit control PCB. Check the power supply.
H03 HIC trouble. DC voltage not detected. Check the HIC. Compressor locked. Check the power supply.
H31 HIC trouble. DC voltage not detected. Check the HIC. Compressor locked. Check the power supply.
L04 Duplication of outdoor unit address. Outdoor unit capacity is not set or setting error. Check the inter-unit control wiring. Replace the outdoor unit EEPROM. Capacity value re-setting.
L10 Indoor unit type setting error. Type of indoor/outdoor units is different. Check the outdoor unit control PCB. Check the type of IU and OU, and re-set address.
L13 4-way valve locked trouble / operation failure. Check the 4-way valve. Check the 4-way valve wiring.
L18 4-way valve locked trouble / operation failure. Check the 4-way valve. Check the 4-way valve wiring. Check the outdoor unit control PCB.
P03 Compressor discharge temperature trouble. Check the discharge temperature sensor (TD). Check the outdoor unit control PCB.
P04 Compressor discharge pressure trouble. Check the refrigerant cycle (gas leak). Trouble with the electronic expansion valve. Valve blockage. Heat exchanger obstruction.
P05 Open phase detected. AC power supply trouble. Check the power supply. Check the reactor wiring. Check the outdoor unit control PCB. Check the compressor wiring.
P13 Valve error. Refrigerant circuit error. Wrong installation for refrigerant piping and wiring. O2 sensor detected. Valve blockage. Check the refrigerant circuit. Check the refrigerant piping and wiring installation. Input from the O2 sensor.
P14 Insufficient gas level detected. Check the refrigerant cycle (gas leak). Trouble with the electronic expansion valve. Valve (or refrigerant circuit) blockage.
P15 Compressor overcurrent trouble. Layer short on the compressor. Compressor locked.
P16 Outdoor unit fan motor trouble. Outdoor unit fan trouble. Check the outdoor unit control PCB. Check the outdoor unit fan motor. Check the outdoor unit control PCB.
P22 Inverter compressor trouble. Check the outdoor unit control PCB. Check the inverter compressor wiring (Open phase/ Reverse phase). Compressor actuation failure (include lock). Valve (or refrigerant circuit) blockage.
P29 Inverter compressor trouble. Check the outdoor unit control PCB. Check the inverter compressor wiring (Open phase/ Reverse phase). Compressor actuation failure (include lock). Valve (or refrigerant circuit) blockage.
P31 Indoor unit in group control trouble. Repair indoor unit which blinking alarm.