Manual for SPW-CR365GXH56

Manual for SPW-CR365GXH56

Brand: SANYO

Category: Air Conditioner

Document Type: Manual

Language: EN

Available Languages: EN , ES

Uploaded: Nov. 21, 2025, 8:14 p.m.

Warranty Information

Warranty information is not detailed in the provided pages.

Basic Operation and Settings

Indoor Unit Addresses

  • After automatic address setting, record the indoor/outdoor unit combination numbers for future reference.
  • To check indoor unit addresses:
    • For single unit connection: Press and hold and buttons for 4 seconds. The address will be displayed.
    • For multiple unit connection (group control): Press and hold and buttons for 4 seconds. Press the UNIT button to cycle through addresses.

Remote Controller Test Run Settings

  • Press the remote controller button for 4 seconds. "TEST" will appear.
  • Test run can be performed in HEAT, COOL, or FAN modes.
  • Outdoor units may not operate for approximately 3 minutes after power ON or operation stop.
  • If errors occur, a code will be displayed. Refer to "2-6. Meaning of Alarm Messages".
  • Press the button again to exit Test Run mode.

Troubleshooting and error codes

LED 1 LED 2 Alarm display Alarm contents Possible cause of malfunction Alarm message
Alternating Alternating LED 1 blinks M times, then LED 2 blinks N times. The cycle then repeats. M = 2: P alarm 3: H alarm 4: E alarm 5: Falarm 6: Lalarm N = Alarm No. Example: LED 1 blinks 2 times, then LED 2 blinks 17 times. The cycle then repeats. Alarm is "P17."
Blinking Blinking Serial communication errors / Mis-setting Error in receiving serial communication signal. (Signal from main indoor unit in case of group control) Ex: Auto address is not completed.
Blinking Blinking Serial communication errors / Mis-setting Error in transmitting serial communication signal.
Blinking Blinking Indoor unit is detecting error signal from remote controller (and system controller). Error in receiving serial communication signal.
Blinking Blinking Indoor unit is detecting error signal from outdoor unit. When turning on the power supply, the number of connected indoor units does not correspond to the number set. (Except R.C. address is "0.")
Blinking Blinking Indoor unit is detecting error signal from outdoor unit. Error of the outdoor unit in receiving serial communication signal from the indoor unit.
Blinking Blinking Improper setting of indoor unit or remote controller. Indoor unit address setting is duplicated.
Blinking Blinking Improper setting of indoor unit or remote controller. Remote controller address connector (RCU. ADR) is duplicated. (Duplication of main remote controller)
Blinking Blinking During auto. address setting, number of connected units does not correspond to number set. Starting auto. address setting is prohibited. This alarm message shows that the auto address connector CN100 is shorted while other RC line is executing auto address operation.
Blinking Blinking During auto. address setting, number of connected units does not correspond to number set. Error in auto. address setting. (Number of connected indoor units is less than the number set)
Blinking Blinking When turning on the power supply, number of connected units does not correspond to number set. (Except R.C. address is "0.") Error in auto. address setting. (Number of connected indoor units is more than the number set)
Blinking Blinking When turning on the power supply, number of connected units does not correspond to number set. (Except R.C. address is "0.") No indoor unit is connected during auto. address setting.
Blinking Blinking Indoor unit communication error of group control wiring. Error of outdoor unit address setting.
Blinking Blinking Indoor unit communication error of group control wiring. Error of main indoor unit in receiving serial communication signal from the sub indoor units.
Alternating Blinking Serial communication errors / Mis-setting Improper setting.
Alternating Blinking Serial communication errors / Mis-setting Duplication of main indoor unit address setting in group control.
Alternating Blinking Serial communication errors / Mis-setting Duplication of outdoor R.C. address setting.
Alternating Blinking Serial communication errors / Mis-setting There are 2 or more indoor units Priority set remote controller controllers which have operation mode priority in refrigerant circuit. Non-priority set remote controller
Alternating Blinking Serial communication errors / Mis-setting Group control wiring is connected to individual control indoor unit.
Alternating Blinking Serial communication errors / Mis-setting Indoor unit address is not set.
Alternating Blinking Serial communication errors / Mis-setting Capacity code of indoor unit is not set.
Alternating Blinking Serial communication errors / Mis-setting Capacity code of outdoor unit is not set.
Alternating Blinking Serial communication errors / Mis-setting Mis-matched connection of outdoor units which have different kinds of refrigerant.
Alternating Blinking Serial communication errors / Mis-setting 4-way valve operation failure
Alternating Blinking Activation of protective device Protective device in indoor unit is activated.
Alternating Blinking Activation of protective device Protective device in indoor unit is activated.
Alternating Blinking Activation of protective device Protective device in indoor unit is activated.
Alternating Blinking Activation of protective device Protective device in indoor unit is activated.
Alternating Blinking Activation of protective device Protective device in indoor unit is activated.
Alternating Blinking Activation of protective device Protective device in indoor unit is activated.
Alternating Blinking Activation of protective device Protective device in indoor unit is activated.
Alternating Blinking Activation of protective device Protective device in indoor unit is activated.
Alternating Blinking Activation of protective device Protective device in indoor unit is activated.
Alternating Blinking Activation of protective device Protective device in indoor unit is activated.
Alternating Blinking Thermistor fault Indoor thermistor is either open or damaged.
Alternating Blinking Thermistor fault Indoor thermistor is either open or damaged.
Alternating Blinking Thermistor fault Indoor thermistor is either open or damaged.
Alternating Blinking Thermistor fault Indoor thermistor is either open or damaged.
Alternating Blinking Thermistor fault Indoor thermistor is either open or damaged.
Alternating Blinking Thermistor fault Outdoor thermistor is either open or damaged.
Alternating Blinking Thermistor fault Outdoor thermistor is either open or damaged.
Alternating Blinking Thermistor fault Outdoor thermistor is either open or damaged.
Alternating Blinking Thermistor fault Outdoor thermistor is either open or damaged.
Alternating Blinking Thermistor fault Outdoor thermistor is either open or damaged.
Alternating Blinking EEPROM on indoor unit PCB failure Protective device for compressor No. 1 is activated.
Alternating Blinking EEPROM on indoor unit PCB failure Protective device for compressor No. 1 is activated.
Alternating Blinking EEPROM on indoor unit PCB failure EEPROM on the outdoor unit PCB is a failure.