Manual for SITOP PSU8200

Manual for SITOP PSU8200

Brand: SIEMENS

Category: Control Unit

Document Type: Manual

Language: EN

Available Languages: EN , ES

Uploaded: Nov. 21, 2025, 7:16 p.m.

Manual Publish Date: 2014-11-01

Warranty Information

No specific warranty period is mentioned in the provided pages.

Overview

1-phase SITOP PSU8200 power supplies are high-performance, regulated DC voltage power supplies for automated systems and machines. They offer a low-profile design with outstanding overload behavior.

Key Benefits:

  • Universal 1-phase line supply compatibility.
  • AC and DC input possible for specific models (6EP1336-3BA10).
  • Adjustable output voltage (24..28.8 V).
  • Power boost (300% rated current for 25 ms) and Extra-Power (1.5x rated current for 5 s) for high inrush currents.
  • Slim width with no lateral mounting clearances required.
  • Wide ambient temperature range (-25 to +70° C).
  • Selectable short-circuit response (constant current or latching shutdown).
  • Soft characteristic for parallel connection to ensure uniform load distribution.
  • 3 LEDs for operating state display.
  • "24 V O.K." signaling contact.
  • Remote ON/OFF control.
  • Expandable with SITOP supplementary modules.

Troubleshooting and error codes

LED Signaling contact, contacts 13-14 Condition
6EP3333-8SB00-0AY0 (24 V/5 A) & 6EP3334-8SB00-0AY0 (24 V/10 A)
Green LED lit Closed Normal operation, output voltage >20 V ±0.5 V
LED off Open (quiescent position) No supply voltage
Yellow LED lit Open (quiescent position) Overload, output voltage <20 V ±0.5 V (only in "constant current" mode)
Red LED lit Open (quiescent position) Latching shut down or remote OFF
6EP1336-3BA10 (24 V/20 A)
LED green (4.1) off Open (quiescent position) No supply voltage
Green LED (4.1) lit Closed Normal operation, output voltage >20 V ±0.5 V
Yellow LED (4.2) lit Open (quiescent position) Overload (Ua <20 V ±0.5 V)
Red LED (4.3) lit Open (quiescent position) Latching shutdown due to overload